PRODUCT
Home / Product
Pressure Module, 4 Ports 125 Pa – 7 kPa – ORMITY 3U Series (pre-sale)
$0.00
Four pressure ports, each with its own range, from ±125 Pa to ±7 kPa, in one 3U plug-in cassette. One module for dust-chamber depression, filter pressure drop and low pressures.
Applications
- Dust chamber enclosure depression – IEC 60529 IP5X / IP6X
- Filter pressure drop
- Nozzle ΔP for calorimeter air flow
Technical data
| Status | Pre-sale – price on quote |
| Ports | 4 × independent, relative to ambient |
| Ranges | P1 ±7 kPa (±1 psi) · P2 ±2.5 kPa · P3 ±500 Pa · P4 ±125 Pa |
| Calculated | ΔP between any two ports |
| Units | Pa, kPa, mbar, psi, Torr, inH₂O |
| Uncertainty | ≤ 1.5 % of full scale (typ. 1 %) |
| Resolution | 1 Pa (P1, P2) · 0.1 Pa (P3, P4) |
| Media | Air and non-aggressive gases |
| Rear connectors | 4 × push-in bulkhead fitting for Ø4 mm tube · RJ45 etherCON |
| Display | 4" IPS touch screen, 480 × 480 px |
| Languages | EN / FR / PT / ES, selectable on screen |
| Communication | Ethernet 10/100 · Wi-Fi 2.4 GHz · Modbus TCP · built-in web page |
| Software | Live values, trends, limits and alarms · data logging with CSV export · network clock and firmware update |
| Calibration | Multi-point correction per channel · certificate data and due date stored · password-protected menu |
| Power supply | PoE IEEE 802.3af through the LAN cable, 48 V DC, 6 W max – no separate supply |
| Format | 3U · 25HP plug-in cassette · front 126.7 × 128.4 mm · depth 70 mm |
| Enclosure | Aluminium, black anodised · markings EN / FR |
| Operating conditions | 0 … 45 °C · 10 … 85 %RH non-condensing · indoor use |
Ref.: ORTYMC-450P
Quantity
Test Principle & Function
Each port has its own sensor and range, so low and high pressures are both read at full resolution. The module shows the selected unit, draws the limit line (e.g. −2.0 kPa) and raises the alarm when it is crossed. ΔP between any two ports is calculated, e.g. chamber versus filter.
Versions & Order Codes
- ORTYMC-410T – Temperature module, Pt100
- ORTYMC-410K – Temperature module, thermocouple K / J
- ORTYMC-420H – Humidity module
- ORTYMC-430A – Ammeter module with trip output
- ORTYMC-440V – Voltmeter module 1000 V
- ORTYMC-450P – Pressure module, 4 ports / 4 ranges
- ORTYMC-460F – Air flow module
- ORTYMC-404R – Rack 4 slots with PoE switch
- ORTYMC-401R – Rack 1 slot, PoE
Ordering, Calibration & Warranty
Pre-sale. Price on quote; lead time confirmed with the quote. Supplied with a factory calibration report; ISO/IEC 17025 calibration certificate available on request. Modules are removable and can be shipped alone for calibration. Warranty: 12 months.